Conductors :
The conductors are drawn from bright electrolytic grade copper, and annealed-conductors are
bunched together. Covering :
The general service normal duty elastomeric compound shall be Type SE 1 confirming to the
requirements of IS 6830: 1984.
The heat resisting, oil resisting and flame retardant (HOFR) normal duty elastomeric compound
shall be Type SE 3 confirming to the requirements of IS 6830: 1984
Thickness of Covering
Nominal Cross-Sectional Area of Conductor
Nominal Thickness of Covering (tc)
(1)
(2)
mm 2
mm
16
2.00
25
2.00
35
2.00
50
2.20
70
2.40
95
2.60
Current Rating of General Serivce Normal Duty Elastomeric Compund Covered Cable with Copper Conductor
Nominal Cross-Sectional Area of Conductor
Current Rating at a Maximum Duty Cycle of
100%
85%
60%
30%
20%
(1)
(3)
(4)
(5)
(6)
(7)
mm2
A
A
A
A
A
16
94
102
121
172
210
25
125
136
161
228
279
35
156
169
201
285
349
50
197
214
254
360
440
70
248
269
320
453
555
95
299
342
386
546
669
Current rating of HOFR Normal Duty Electomeric Compound Covered Cable with Copper Conductor