Cables for fixed wiring applications, PVC insulated Sheathed / Unsheathed with plain annealed electrolytic copper conductor conforming to IS: 694:1990 for working voltages upto and including 1100V.
Area Sq. mm.
No. & Dia. Of Wires (Nom.) mm
Unsheathed Cables
Sheathed Cables
Max. DC Conductor Resistance @ 200 C
Current Rating ampere
Insulation Thickness (Nom.) mm
Approx.
Overall
Diameter
mm
Insulation Thickness (Nom.)
mm
Sheath Thickness (Nom.)
mm
Approx.
Overall
Diameter
mm
1.0
1/1.13
0.7
2.6
0.6
0.8
4.1
18.1
10
1.5
1/1.38
0.7
2.9
0.6
0.8
4.4
12.1
14
2.5
1/1.78
0.8
3.5
0.7
0.8
5.0
7.41
20
4
1/2.25
0.8
4.0
0.8
0.9
5.85
4.61
26
4
7/0.85
0.8
4.3
0.8
0.9
6.1
4.61
26
6
1/2.76
0.8
4.5
0.8
0.9
6.4
3.08
35
6
7/1.04
0.8
4.9
0.8
0.9
6.7
3.08
35
10
7/1.35
1.0
5.7
1.0
0.9
7.55
1.83
44
16
7/1.7
1.0
7.2
1.0
1.0
9.3
1.15
55
25
7/2.14
1.2
8.9
1.2
1.1
11.2
0.727
75
35
19/1.53
1.2
10.0
1.2
1.2
12.3
0.524
90
50
19/1.78
1.4
11.9
1.4
1.2
14.4
0.387
120
70
19/2.14
1.4
13.6
-
-
-
0.268
150
95
19/2.52
1.6
15.8
-
-
-
0.193
175
Cables for fixed wiring applications, PVC insulated with plain annealed electrolytic copper conductor conforming to BS:2004 for working voltages upto and including 250V.
Nominal Area in Sq. inches
No. & Dia. Of Wire in inches
Thickness of Insulation in inches
Overall Dia. in inches
Current Rating ampere
0.0015
1/0.044
0.035
0.119
5
0.002
3/0.029
0.035
0.137
10
0.003
3/0.036
0.035
0.153
15
0.0045
7/0.029
0.035
0.162
20
0.007
7/0.036
0.040
0.193
28
0.01
7/0.044
0.040
0.217
36
0.0145
7/0.052
0.040
0.241
43
0.0225
7/0.064
0.040
0.277
53
The data and information given herein are purely as a guide. VIRAL takes no responsibility for