Cables shall only be operated at their full
rating if the minimum current at which circuit protection is designed to operate does not
exceed 1.5 times (in the case of cables in air or in ducts) or 1.3 times (in the case of
cables laid direct in the ground) the values tabulated.
Note : For cables in air, no reduction
in current rating is necessary provided that
1. The horizontal clearance between circuits is :
(a) not less than six times the overall diameter of an individual cable, and
(b) not less than the overall width of an individual circuit, except that the horizontal
clearance need not in any case exceed 15 cm.
2. The vertical clearance between circuits is not
less than 15 cm
3. If the number of circuits exceeds 4, they are
installed in a horizontal plane.
However, for installation conditions other than
above, current rating factors incorporated in IS:3961 Part II may please be applied.
Short Circuit Rating in K.
ampere for One Second duration : |